As AI training clusters scale into the hundreds of megawatts, utilities and ISOs are confronting a load category that conventional planning tools weren't built to represent. In a new technical paper co-authored with experts at the National Laboratory of the Rockies, Kevin Chen and Billy Yancey of EPE recently addressed this with a measurement-based approach to modeling the electrical signature of Graphics Processing Unit (GPU) compute racks.
The power demanded by data centers housing AI workloads varies rapidly based on the computational intensity of the tasks executed by the GPUs running these workloads. Load modeling has become an important part of data center design and evaluation, used in domains from planning to operations.
GPU modeling resists conventional approaches for four reasons:
There is also a gap in current practice worth noting: existing models relate the phase of computation to power consumption but tend to consider three-phase power in aggregate and discard the inherently unbalanced nature of the load, leaving the voltage-current relationship unexplored. That relationship, called admittance, is the focus of this work.
Rather than modeling the GPU's internal power electronics from first principles, this work takes a data-driven route: admittance is developed via spectral analysis on measured voltage and current, creating a model that is linear time-invariant, easily implementable in simulations, and requires no online parameter storage.
The formulation preserves phase imbalance rather than averaging it away: discarding coupling between phases, the admittance is modeled as a 3×3 diagonal matrix, with phases considered separately given that GPU loads are inherently unbalanced. This yields three independent single-input, single-output identification problems rather than one aggregate model.
A key simplification follows from the power-conditioning hardware itself: due to the ubiquitous presence of power factor correction circuits in GPUs, the voltage and current are in phase, displaying a resistive behavior of the GPU load and letting the admittance magnitude spectrum be treated as dominantly resistive.
Because workload intensity shifts continuously, two versions of the model are derived from the same measurement stream: a 1-cycle model, based on the 1-cycle measurements of voltage and current for the lowest-order snapshot, and an N-cycle model (nine consecutive cycles here), which resolves finer frequency structure at the cost of absorbing workload drift across the window.
The pipeline follows five steps:
1. Extract frequency content via FFT.
2. Form an admittance spectrum as the bin-wise ratio of current to voltage magnitude.
3, Fit a narrowband resonant transfer-function section to each retained bin, where a specific transfer function evaluates a prescribed gain and zero phase angle at a chosen frequency, and is approximately zero elsewhere.
4. Sum those sections into a parallel bank per phase.
5. Reduce order by thresholding out insignificant bins based on separate voltage and current magnitude thresholds.
The model was built and validated against field data from an operating HPC facility, not synthetic signals.

For teams supporting data center interconnection studies, GI/SIS work, or large-load planning submittals, this measurement-grounded, EMT-ready load representation addresses a real gap. Most present-day data center load models used in interconnection studies still rely on aggregate, balanced power assumptions that this work shows may understate both harmonic content and phase imbalance.
It's worth being transparent about current limitations: the model is time-invariant by construction even though the underlying load is not, a contribution that grows with window length. Planned extensions include additional benchmark cases with temperature and workload-type data, deployment in a commercial EMT tool with performance reporting on unseen workloads, exploration of linear time-periodic and harmonic-state-space approaches, and eventual study of data center grid interaction as an unbalanced load.
As AI-driven load growth continues to reshape interconnection queues, capacity planning, and grid reliability studies nationwide, measurement-based approaches like this admittance model represent a meaningful step toward more accurate representation of GPU infrastructure.
EPE's power systems engineers are actively tracking these developments and applying rigorous, field-validated modeling techniques to help clients navigate the unique technical and regulatory challenges that data center and large-load interconnections present. To start the conversation, reach out to our team of data center and power systems experts using the form below.
We're here to help.
When you partner with EPE, you get an experienced team dedicated to providing you with tailored solutions and expert guidance.
Please fill out the form to the right, and a member of our team will be in touch.